[1] Functions and Factory Settings of the Dipswitches
1. Heat source unit
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Heat source Unit" for details.(page 143)
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch
Before power on
C
C
SW1
1-10
For self-diagnosis/
operation monitoring
Refer to the LED monitor display on the
heat source unit board.
Anytime after power on
C
C
SW2
1
Centralized control
switch
Without connection
to the centralized
controller
With connection to
the centralized con-
troller
Before power on
B
B
2
Deletion of connec-
tion information
Normal control
Deletion
Before power on
A
-
3
Deletion of error his-
tory SW
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
to ON)
C
C
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
4
Pump down mode
Normal control
Pump down mode
After being energized and
while the compressor is
stopped
A
-
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
Power on signal out-
put switch
During Thermo-ON
During Thermo-
OFF
Anytime after power on
A
-
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......