IX
Troubleshooting ]
- 335 -
HWE09080
GB
(2) Inverter output related troubles
Items to be checked
Phenomena
Remedy
[1]
Check the
INV board er-
ror detection
circuit.
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Overcurrent error
Error code: 4250
Detail code: No. 101, 104, 105,
106, and 107
Replace the INV board.
(2)
Put the heat source
unit into operation.
2)
Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
4)
IPM open
Error code: 5301
Detail code: No.119
Normal
[2]
Check for
compressor
ground fault
or coil error.
Disconnect the compressor
wiring, and check the com-
pressor Meg, and coil resis-
tance.
1)
Compressor Meg failure
Error if less than 1 Mohm.
Check that there is no liquid re-
frigerant in the compressor.
If there is none, replace the com-
pressor.
2)
Compressor coil resistance failure
Coil resistance value of 1 ohm
(20°C [68°F])
Replace the compressor.
[3]
Check wheth-
er the inverter
is damaged.
(No load)
(1)
Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
1)
Inverter-related problems are de-
tected.
Connect the short-circuit connec-
tor to CN6, and go to section [1].
(2)
Disconnect the short-
circuit connector from
CN6 on the INV
board.
2)
Inverter voltage is not output at the
terminals (SC-U, SC-V, and SC-W)
Replace the INV board.
(3)
Put the heat source
unit into operation.
Check the inverter
output voltage after
the inverter output
frequency has stabi-
lized.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
4)
There is no voltage imbalance be-
tween the wires.
Normal
*Reconnect the short-circuit con-
nector to CN6 after checking the
voltage.
[4]
Check wheth-
er the inverter
is damaged.
(During com-
pressor oper-
ation)
Put the heat source unit into
operation.
Check the inverter output
voltage after the inverter
output frequency has stabi-
lized.
1)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
[YHMU-A]
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......