IX
Troubleshooting ]
- 268 -
HWE09080
GB
1. Error
Code
Transmission line bus busy error
2. Error definition and error detection method
Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy
Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause, check method and remedy
1. Error
Code
Communication error between device and transmission processors
2. Error definition and error detection method
Communication error between the main microcomputer on the indoor unit board and the microcomputer for transmission
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause, check method and remedy
6603
Cause
Check method and remedy
(1)
The transmission processor cannot be transmit-
ted as the short-wavelength voltage like noise ex-
ists consecutively on the transmission line.
No noise indicates that the error source controller is a fail-
ure. If noise exists, investigate the noise.
-> No noise indicates that the error source controller is a
failure.
-> If noise exists, investigate the noise.
(2)
Error source controller failure
6606
Cause
Check method and remedy
(1)
Data is not properly transmitted due to accidental
erroneous operation of the controller of the error
source.
Turn off the power source of the heat source and the in-
door units.(When the power source is turned off separate-
ly, the microcomputer will not be reset, and the error will
not be corrected.)
-> If the same error occurs, the error source controller is
a failure.
(2)
Error source controller failure
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......