[2-2 Types and Maximum Allowable Length of Cables ]
2
-
chapter 2
BS_02_C
2
Rest
rict
io
ns
2-2
Types and Maximum Allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man-
ual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference.
(Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission cable. Doing so will damage the electronic compo-
nents on the terminal block.
6) Use 2-core shielded cables as transmission cables.
Do not use a single multiple-core cable to connect indoor units that belong to different refrigerant systems. Doing so may result
in signal transmission errors and malfunctions..
7) When extending the transmission cable, be sure to extend the shield wire.
(2) Control wiring
Different types of control wiring are used for different systems. Before performing wiring work, refer to the following page(s).
[2-7 Example System with an MA Remote Controller]
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line.
Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce
noise interference.
1) M-NET transmission line
Cable type
Facility
type
All facility types
Type
Shielded cable CVVS, CPEVS, MVVS
Number of
cores
2-core cable
Cable size
Larger than 1.25mm
2
[AWG16]
Maximum transmission
line distance between the
outdoor unit and the far-
thest indoor unit
200 m [656ft] max.
Maximum transmission
line distance for central-
ized control and Indoor/
outdoor transmission line
(Maximum line distance
via outdoor unit)
500m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
TB3:Terminal block for transmission line connection
TB7:Terminal block for transmission line for centralized control
multiple-core cable
2-core shielded cable
2-core shielded cable
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
TB3
TB7
TB3
TB7
TB3
TB7
TB3
TB7
0000004492.BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...