[8-9 Troubleshooting Inverter Problems ]
BS_08_C
chapter 8 -
27
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-9-2
Checking the Inverter Board Error Detection Circuit
*1 Output voltage is present at the inverter output wiring terminal. To avoid short-circuiting and ground fault, do not let the
terminal come in contact with the unit or the compressor, and use caution not to damage the terminal.
*2 Compressors on P200, P250, and P300 models are located in the back of the MAIN BOX. To disconnect the inverter output
wiring, move the MAIN BOX out of the way first, and then disconnect the wiring from the terminal on the compressor. Refer
to [8-12-1 Ensuring Maintenance Space (Preparation for the Maintenance of Refrigerant Circuit Parts)] for how to move the
MAIN BOX.
8-9-3
Checking the Compressor for Ground Fault and Coil Resistance Problems
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Remove power supply.
1)
Overcurrent error
Error code: 4250
Detail code: No. 101, 104, 105, 106, and
107
Replace the INV board.
(2)
Disconnect the inverter
output wires from the
compressor terminals (U,
V, W).
*1
2)
Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
(3)
Apply power supply.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
(4)
Put the outdoor unit into
operation.
4)
IPM open
Error code: 5301
Detail code: No.119
Normal
Items to be checked
Phenomena
Remedy
Disconnect the compressor wir-
ing, and check the compressor
Meg, and coil resistance.
1)
Compressor Meg failure
Error if less than 1 M
Ω
.
Check that there is no liquid refrigerant
in the compressor.
If there is none, replace the compres-
sor.
2)
Compressor coil resistance failure
Coil resistance value of 0.325
Ω
(20°C [68°F]): P250 model
Replace the compressor.
0000004498.BOOK 27 ページ 2018年1月5日 金曜日 午前10時38分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...