[5-2 Outdoor Unit Control ]
12
-
chapter 5
BS_05_C
5
Cont
rol
5-2-8
Outdoor Unit Fan Control
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter, targeting a constant
evaporation temperature of (0°C [32°F]= 0.71 MPa [103 psi]) during cooling operation.
The OS in the multiple-outdoor-unit system operates at the actual outdoor unit fan control value that is calculated by the OS
based on the preliminary outdoor unit fan control value that the OC determines.
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.(Only when TH7<0°C [32°F])
5-2-9
Subcool Coil Control (Linear Expansion Valve <LEV1>)
The OC and OS controls the subcool coil individually.
The LEV is controlled every 30 seconds to maintain constant the subcool at the outdoor unit heat exchanger outlet that is
calculated from the values of high pressure (63HS1) and liquid piping temperature (TH3), or the superheat that is calculated
from the values of low pressure (63LS) and the bypass outlet temperature (TH2) of the subcool coil.
LEV opening is controlled based on the values of the inlet (TH6) and the outlet (TH3) temperatures of the subcool coil, high
pressure (63HS1), and discharge temperature (TH4). In a single-outdoor-unit system, the LEV is closed (0) during cooling
Thermo-OFF. In a multiple-outdoor-unit system, the LEV closes (0) during cooling Thermo-OFF.
5-2-10
Refrigerant Flow Control (Linear Expansion Valves <LEV2a and LEV2b>)
The valve opens to a specified angle during cooling (Opening: 2100 pulses)
Valve opening is controlled based on the values of high pressure (63HS1), discharge temperature (TH4), low pressure
(63LS), and piping temperature (TH5).
The valve moves to the predetermined position while the unit is stopped.
The valve opening may increase to 3000 pulses during the units are operated in unusual operating conditions.
5-2-11
Control of Controller Cooling Function (Electronic Expansion Valve <LEV9>)
Control of controller cooling function is performed individually for OC and OS.
The opening of LEV9 is adjusted every three seconds to keep the controller heatsink temperature (THHS) below the threshold
value, which is determined by the setting of the outside temperature (TH7).
5-2-12
Control at Initial Startup
When started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode.
At the completion of the initial operation mode on the OC and OS, they will go into the normal control mode.
(1) P250YNW model
50 F 60Hz
or F < 50Hz
Initial startup mode starts.
Completed in the integrated operation time of 35 minutes.
Initial startup mode complete
or the discharge superheat (TH4 - Tc) is detected (within
5 minutes of startup) that remains above approximately
25 degrees for one minute or if the shell bottom SH
(TH15-Te) is 15 deg or above (for continuous 5 minutes)
10 minutes after start up.
Completed in the integrated operation time of 90 minutes.
0000004495.BOOK 12 ページ 2017年12月26日 火曜日 午前11時44分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...