[3-4 Functions of the Major Components of Outdoor Unit ]
14
-
chapter 3
BS_03_C
3 Major Compon
ent
s
, Their Fun
ct
io
ns
a
n
d
Re
frig
e
ra
n
t
Circ
ui
ts
Sole-
noid
valve
SV1a
Discharge-
suction
bypass
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
AC220-240V
Open while being powered/
closed while not being pow-
ered
Continuity check
with a tester
SV2
Makes excessive refrigerant in the
accumulator evaporate
Open while being powered/
closed while not being pow-
ered
SV9
High-pressure-rise prevention
Open while being powered/
closed while not being pow-
ered
SV10
-
Open while being powered/
closed while not being pow-
ered
SV11
-
Open while being powered/
closed while not being pow-
ered
Linear
expan-
sion
valve
LEV1
(SC control)
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
DC12V
Opening of a valve driven by a
stepping motor 0-480 pulses
Same as indoor
LEV
The resistance val-
ue differs from that
of the indoor LEV.
Refer to the follow-
ing page(s). [8-8
Troubleshooting
LEV Problems]
LEV9
(Refrigerant
flow adjust-
ment)
Adjusts the flow of refrigerant by-
passed from the pipe for cooling
the control board when the control
board temperature rises
LEV2a
(Refrigerant
flow adjust-
ment)
-
DC12V
Opening of a valve driven by a
stepping motor 2100 pulses
(Max. 3000 pulses)
Continuity check
with a tester
Continuity between
white and orange.
Continuity between
yellow, red, and
blue.
LEV2b
(Refrigerant
flow adjust-
ment)
4-way
valve
21S4a Control
refrigerant
distribution
(OC and OS)
AC220-240V
Continuity check
with a tester
21S4b Control
refrigerant
distribution
(OC and OS)
Heat exchanger capacity control
AC220-240V
Fan
motor
FAN motor 1
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
AC380-400V, 920W
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Yellow
White
Orange
red
Blue
M
0000004493.BOOK 14 ページ 2018年1月5日 金曜日 午前9時11分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...