[5-3 Indoor Unit Control ]
BS_05_C
chapter 5 -
23
5
Cont
rol
-7- Switching Between Pulse and Level of MA Remote Controller External Input
The start/stop operation can be performed by either of the MA remote controller or the external input (pulse/level).
Input
DIPSW on the address circuit board (No.1 and No. 2)
Function
Start/Stop
Usage
Sending ON/OFF
command to the
indoor unit
Signal specifications
Pulse (With-voltage/No-voltage a-contact) *
<In case of with-voltage>
Power supply:12~24V DC Electrical current:10mA (12V DC)
(Pulse powering time) (Pulse interval)
<Pulse specification>
over 200ms
Valid operation
External input (level)
External input (pulse)
MA remote controller
SW1-10 = ON
SW1-10 = OFF
SW1-9 = OFF
SW1-9 = ON
* For the MA remote controller and the external input, the operation command sent later has no priority.
* The manipulator for centralized control can be operated regardless of the SW1-9 status (ON),
and SW1-10 status (OFF).
* When the Normal/Inspection switch on the main unit is set to "Inspection", the external input will be disabled.
Only the operation performed by the MA remote controller is valid.
* Use a contact point for small electrical current (12V DC 1mA).
-8- Operation during Electrical Power Failure
After the controller in this air conditioning unit receives signals indicating power failure or an instantaneous
drop in voltage, unless the unit receives a command not to restart, it will resume its operation after power
supply is restored.
Depending on the duration of power outage, the following operations will be run.
Note 1: When indoor unit is in the maintenance mode , it will not resume operation even after the power has
been restored.
Note 2: After the unit resumes its operation, MA remote controller will display 'HO' for fifteen seconds,
during
which time the MA remote controller will not respond. To turn off the unit during this time, turn off the
power with an electric leak breaker.
Duration of Power Outage
Unit Operation
Shorter than 6msec
Both indoor and outdoor units will stay on.
Longer than 6msec and
Shorter than 50msec
(Note1, Note2)
It is recognized by the unit as aninstantaneous power outage
Indoor Unit: The fan stays on.
Outdoor Unit: Compressor stops, then resumes its operation 20 seconds later.
Longer than 50msec
(Note1, Note2)
It is recognized by the unit as power outage.
Air-conditioning unit will stop (incl. fan and compressor).
It will resume operation after the power has been restored.
* The time it takes for the indoor unit fan to resume its operation after power failure is as follows:
20 s (indoor unit address/2) seconds (55 seconds max.).
* The compressor on the outdoor unit will resume its operation according to the operation signal
from the indoor units after 30 seconds since power restoration.
over 200ms
External input-output
board (IFB)
The case of with-voltage input ... A
The case of no-voltage input .... B
When using the external input function on the indoor unit
that is connected to a two-refrigerant circuit, connect the
short-circuit plate that is supplied with the unit to the
appropriate terminals on the external input-output board.
AC
A1
A2
BC
B1
B2
A
B
TB23
TB21
0000004495.BOOK 23 ページ 2017年12月26日 火曜日 午前11時44分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...