[8-1 MA Remote Controller Problems ]
4
-
chapter 8
BS_08_C
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-1-4
Air Conditioning Units Do Not Operate When the ON Button Is Pressed.
1. Phenomena
Even if the operation button on the remote controller is pressed, the indoor and the outdoor units do not start running.
2. Check method and remedy
YES
Blinking?
Is " " displayed on
the remote controller?
NO
NO
NO
YES
YES
When all wires used for
grouping are disc
onnected, is a
t
least one
of the L
ED2 on the
grouped i
ndoo
r units lit?
YES
Replace the MA
remote controller
.
Is there an indoor unit on
which LED2 is turned of
f?
If operated afterwards,
error 6602 or
6607 occurs.
Check the voltage between
the MA
remote controller
terminals (A
and B).
9-13VDC if the voltage is applied
and 0V if no voltage is applied.
Is LED1 on the indoor unit
control board lit?
(Blinks for 2 or 3 seconds
approximately every
20 seconds)
Does the number of the MA
remote controllers that are
connected to an indoor
unit exceed the allowable
range (2 units)?
Blinking?
(T
urns on momentarily
approximately every
20 seconds)
In the case of MA
remote
controller
, see item 1.
In the case of MA
remote
controller
, see items 1 and 2.
In the case of MA
remote
controller
, see item 3.
In the case of MA
remote
controller
, see item 2.
In the case of MA
remote
controller
, see item 2.
Check for the M-NET
transmission line.
Replace the indoor unit control board.
Connect 2 remote controllers or less.
*After correcting the error
, daisy-chain
the wire for the MA
remote controller again.
Check whether the screw
on the wire is not loose.
Is LED2 on the indoor unit
control board blinking?
When the unit is operated with
the remote controller
, will "ON"
appear on the display?
Is "Centralized"
displayed?
"HO"/"PLEASE W
AIT" keeps
blinking on the MA
remote controller
.
Is only the power source of the
indoor unit turn turned on again?
DEMAND by MELANS?
External thermo
input setting?
(SW3-3=ON)
Does an error occur when
the power is reset?
Does the unit work properly
when the wire for the MA
remote controller is
daisy-chained again?
Is LED1 on the indoor
unit control board lit?
Does the MA
remote controller
work properly when it is connected
to the specified indoor unit?
Does an error occur when
the power is reset?
Running group operation with
the MA
remote controller?
Are there any indoor
units for computer rooms in
the group?
No problems are found with the
computer room indoor unit.
Does an error occur when
the power is reset?
Check that no error occurs in other indoor units.
Check the indoor unit on
which LED2 is lit.
All the indoor unit
power failure?
All the indoor unit
power failure?
Error display?
Error display?
Thermo is OFF?
Is operation possible?
Short circuit of the
remote controller?
After turning the power on, check whether "HO"/
"PLEASE W
AIT" is displayed on the remote controller
.
After more than 20 seconds since
turning the power on, is LED2 check
of the indoor control board still
displayed?
Is the operation by MELANS
forbidden or the input from external control
equipment allowed (SWC=ON)?
Is the compulsory
thermo OFF (SW
A)
switch set to "2" or "3"?
Although No.1 refrigerant circuit
is normal, No.2 or No.3
refrigerant circuit remain stopped.
Running group operation with
the MA
remote controller?
Does the indoor unit make
an instantaneous stop?
Power supply voltage
AC188~253V?
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
When no error occurs
NO
NO
NO
Keep displaying
for 5 or more minutes.
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Check the
power supply
.
Check the wire for
the remote controller
.
NO
Replace the indoor unit control board.
NO
NO
NO
NO
NO
Replace the MA
remote controller
.
NO
Replace the remote controller
or the indoor control board.
YES
Replace the indoor unit control
board where an error occurs.
Keep the operation.
NO
NO
NO
NO
Keep the operation.
YES
YES
YES
YES
Power on
YES
Refer to the self-diagnosis list
for the displayed error code.
YES
Normal
T
u
rns of
f within approximately 5 minutes.
After the main power on, start the MA
remote
controller
. "HO" display will appear
.
YES
Normal
"Centralized" is displayed.
YES
Refer to the error code list.
YES
YES
YES
Normal
YES
Normal
(Is the thermo OFF
signal input?)
YES
Set the SW
A
to "1".
YES
Refer to the self-diagnosis list for
the displayed error code.
YES
YES
YES
YES
Check the equipment
package indoor unit.
YES
Replace the remote controller or
the indoor control board.
Replace the indoor unit control board.
YES
YES
YES
Replace the remote controller
or the indoor control board.
Normal
(Operate the unit with
external control equipment)
YES
YES
Replace the indoor
unit control board.
Check the
power supply
.
YES
YES
YES
YES
Check the voltage
between the MA
remote controller
terminal blocks (TB15) (A
and B).
9-13VDC if the voltage
is applied and 0V if no voltage
is applied.
NO
Disconnected wire for
the remote controller?
Disconnected wire to
the terminal block?
Disconnected relay connector?
NO
Are the length or the diameter
of the wire for MA
remote controller
out of specification?
NO
YES
YES
Use the wire that meets the specification.
Replace the wire for the MA
remote controller
.
YES
Check for the wire for
the remote controller
.
Keep the operation.
YES
Replace the indoor
unit control board.
YES
YES
YES
Power on
In the case of MA
remote
controller
, see item 1.
0000004498.BOOK 4 ページ 2018年1月5日 金曜日 午前10時38分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...