[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
14
-
chapter 7
BS_07_C
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-2
Error Code [4106]
1. Error code definition
<Transmission power supply fault Error detail code FF (Outdoor unit)>
2. Error definition and error detection method
Transmission power output failure
3. Cause
1) Wiring failure
2) Transmission power supply cannot output voltage because overcurrent was detected.
3) Voltage cannot be output due to transmission power supply problem.
4) Transmission voltage detection circuit failure
4. Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-10-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit]
1. Error code definition
<Transmission power supply fault other than error detail code FF (Outdoor unit)>
2.Error definition and error detection method
Transmission power reception failure
3.Cause
One of the outdoor units stopped supplying power, but no other outdoor units start supplying power.
4.Check method and remedy
Check the transmission power supply circuit on all outdoor units in a given refrigerant circuit for problems. [8-10-2 Trouble-
shooting Problems with Outdoor Unit Transmission Power Supply Circuit]
7-6-3
Error Code [4109]
1. Error code definition
Indoor unit fan fault
2. Error definition and error detection method
If the auxiliary relay X4 (for fan fault detection) remains unexcited for a certain period of time, the unit will come to an abnormal
stop, and the fan output goes off.
Overcurrent breaker trigger value
3. Cause, check method and remedy
Model name, motor output
Preset value
PFD
P250 model, 3.7kW
7.5A
P500 model, 5.5kW
12A
Cause
Check method and remedy
(1)
Overcurrent breaker (51F) is tripped.
Check the fan for proper rotation, check for worn bear-
ings, and check the pulley for proper alignment.
Check for proper belt tension (esp. overtension).
Check the motor for proper operation.
51F malfunction (Test switch is left to ON.)
(2)
Blown fuse (F1)
Check for a loose or blown fuse
(3)
Auxiliary relay (X4) fault
Loose, broken, or incorrect lead wire wiring
Coil fault, contact failure
(4)
Broken wire
Check for broken wire.
(5)
Loose connector
Check the connector for proper connection.
(6)
Indoor unit control board (I.B1, I.B2) fault
If no problems are found with the items above and if the
problem persists, circuit board failure is suspected.
0000004497.BOOK 14 ページ 2017年12月26日 火曜日 午前11時46分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...