Error Code Definitions and Solutions: Codes [1000 - 1999]
7-3-1
Error Code [1102]
1. Error code definition
Discharge temperature fault
2. Error definition and error detection method
1) If the discharge temperature sensor detects a temperature of 120° C [248°F] or higher during operation (first detection), the
outdoor unit stops, goes into the 20-second restart delay mode, and automatically restarts after twenty seconds.
2) If the discharge temperature sensor detects a temperature of 120°C [248°F] or higher again (second detection) within 30 min-
utes of the first stoppage of the outdoor unit as described above, the outdoor unit stops again, goes into the 20-second restart
mode, and restarts after 20 seconds.
3) If the discharge temperature of 120°C [248°F] or more is detected (the 30th detection) within 30 minutes after the stop of the
outdoor unit described above (regardless of the first or the 29th stop), the outdoor unit will make an error stop, and the error
code "1102" will be displayed.
4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor
unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.
5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the
LED display.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Gas leak, gas shortage
Refer to the following page(s). [6-3 Evaluating and Adjusting
Refrigerant Charge]
(2)
Overload operation
Check operating conditions and operation status of indoor/
outdoor units.
(3)
LEV failure on the indoor unit
Perform a cooling operation to check the operation.
Cooling: Indoor unit LEV, LEV1, LEV2
Refer to the following page(s). [8-8 Troubleshooting LEV
Problems]
(4)
Outdoor unit LEV1 actuation failure
Outdoor unit LEV2 actuation failure
(5)
Closed refrigerant service valve
Confirm that the refrigerant service valve is fully open.
(6)
Outdoor fan (including fan parts) failure, mo-
tor failure, or fan controller malfunction
Rise in discharge temp. by low pressure
drawing for (3) - (6).
Check the fan on the outdoor unit.
Refer to the following page(s). [8-7 Troubleshooting Outdoor
Unit Fan Problems]
(7)
Gas leak between low and high pressures
(4-way valve failure, Compressor failure, So-
lenoid valve (SV1a) failure)
Perform a cooling operation and check the operation.
(8)
Thermistor failure
(TH4)
Refer to the following page(s). [7-7-2 Error Codes
[5102,5103,5104,5105,5106,5107,5115]]
(9)
Input circuit failure on the controller board
thermistor
Check the inlet air temperature on the LED monitor.
0000004497.BOOK 6 ページ 2017年12月26日 火曜日 午前11時46分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...