8-12-1
Ensuring Maintenance Space (Preparation for the Maintenance of Refrigerant
Circuit Parts)
1. S-module
Take the following procedures to ensure sufficient maintenance space and good visibility.
Figure 1
Drain pan
Figure 2
Drain pan cover
Figure 4
Top attachment
Bottom attachment
Main control box
Inverter control box
Figure 5
Figure 6
cable tie
Cable strap
Cable strap
cable tie
Figure 7
cable tie
Figure 3
Rod holder
Drain pan cover
Silicon tube
Defrost pipe
(1) Remove the front panel from the unit by unscrewing the eight screws. (See Figure 1.) *Figure 1 shows the unit without the
front panel.
(2) Remove the drain pan cover by unscrewing the screw and cutting the cable tie. (See Figures 2 and 3.)
When re-placing the drain pan cover after the completion of maintenance work, make sure that the silicon tube is properly placed
on the defrost pipe, and then fix the drain pan cover in place with a cable tie. (Figures 2 and 3 show the cable ties to be cut.)
(3) Remove the drain pan by unscrewing the two screws. (See Figure 2.)
Be sure to remove the two rod holders holding the check joints to the drain pan. (See Figure 3.)
(4) Remove the top attachment connecting the main control box and the inverter control box by unscrewing the two screws.
(See Figure 4.)
(5) Remove the bottom attachment connecting the main control box and the inverter control box by unscrewing the two screws.
(See Figure 4.)
(6) Remove the cover from the main control box by unscrewing the three screws. (See Figure 5.)
(7) Cut the two cable ties holding the weak electrical wiring inside the main control box in place, and loosen the four cable
straps holding the weak and strong electrical wirings. (See Figure 6.)
(8) Cut the two cable ties holding the rubber bush at the bottom of the main control box. (See Figure 6.)
(9) Cut the three cable ties and loosen the two cable straps holding the weak electrical wiring outside the main control box.
(See Figure 7.)
Cable strap for
holding weak
electrical wiring
(front)
Cut the cable tie.
Cut the cable tie.
0000004498.BOOK 45 ページ 2018年1月5日 金曜日 午前10時38分
Summary of Contents for PFD-P250VM-E
Page 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Page 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Page 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Page 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Page 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Page 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Page 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Page 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...