216
(4) Error log No.2 to No.64 (buffer memory address: 2080 to 3087 (820
H
to C0F
H
))
In the same sequence as error log No.1, information on error log No.2 to No.64 is stored.
Appendix 1.5
Ethernet port line status
(1) Communication status (buffer memory address: 3328 (D00
H
))
The communication status data of the Ethernet port is stored in the following bit pattern.
1) Empty
2) Communication mode
0: Half-duplex
1: Full-duplex
3) Connection status
0: Hub or external device not connected or disconnected
1: Hub or external device connected
4) Empty
5) Data transmission speed
00: Empty
01: Operating at 100BASE-TX
10: Operating at 1000BASE-T
11: Empty
2072 to 2075
(818
H
to 81B
H
)
Date and time
The date and time of the error is stored in the following BCD code.
2076
(81C
H
)
Command code
A command code for the message of the error is stored.
A value is stored only when the error occurred in SLMP communication.
0: No error (default) or an error lower than the TCP or UDP level
Other than 0: Command code
2077
(81D
H
)
Subcommand code
A subcommand code for the message of the error is stored.
A value is stored only when the error occurred in SLMP communication.
0: No error (default) or an error lower than the TCP or UDP level
Other than 0: Subcommand code
2078 to 2079
(81E
H
to 81F
H
)
System area
Address
Name
Description
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
00
H
(Sun.) to 06
H
(Sat.)
Day of week (00
H
to 06
H
)
Year (00
H
to 99
H
), first 2 digits
Year (00
H
to 99
H
), last 2 digits
b15
b8 b7
b0
2072(818
H
)
2073(819
H
)
2074(81A
H
)
2075(81B
H
)
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
1)
2)
3)
4)
5)
3328(D00
H
)
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......