CHAPTER 9 TROUBLESHOOTING
9
9.
5
Er
ror C
o
de List
D2B0
H
Transient transmission failed
• Check if the cable of the request source and the switching hub are
connected properly.
• Exchange the cables between PORT1 and PORT2 at the request source
and retry the operation.
• Reduce the frequency of transient transmission and then retry the
operation.
D2E0
H
IP communication test in progress
Retry the IP communication test after a while. (Up to four IP communication
tests can be concurrently executed.)
D2E1
H
IP communication test execution error
(no response to Ping)
• Check "Communication Target" in the "IP Communication Test" dialog box.
• Check and correct the status of the cable connection and line between the
CC-Link IE Field Network gateway setting station and the communication
destination.
• Enable a response to the Ping command (ICMP echo request) in the
firewall settings on the external device or antivirus software.
D2E2
H
No IP address distribution
An IP address is not distributed to the destination Ethernet adapter module
(CC-Link IE Field Network part). Take the following actions to distribute an IP
address.
• Set an IP address to the master station.
• Use a master station that supports the IP packet transfer function.
After taking the actions above, check that baton pass becomes enabled.
Then execute the IP communication test again. The baton pass status can
be checked using Baton pass status (own station) (SB0047, SW0047).
D2E3
H
No CC-Link IE Field Network gateway
setting
• Check that the CC-Link IE Field Network gateway setting is configured
and is correct in the destination Ethernet adapter module.
• Check the IP address of the master station.
Take the actions above then execute the IP communication test again.
D2E4
H
IP address out of range (Ethernet part
of the destination Ethernet adapter
module)
When the IP address of the destination Ethernet adapter module (Ethernet
part) is the same as the network address of the master station, set the IP
address within the following range.
• Third octet: 1 to 239
• Fourth octet: 1 to 120
Change the IP address of the CC-Link IE Field Network in the master station
so that the IP address of the Ethernet adapter module (Ethernet part) may
differ from the network address of the master station.
D501
H
Communication LSI failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
D502
H
MAC address error
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
D529
H
to D52A
H
RAM failure
• Malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Perform a unit test on the Ethernet adapter module. If the failure occurs
again, the hardware of the Ethernet adapter module may be faulty. Please
consult your local Mitsubishi representative.
Error code
Error
Action
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......