169
CHAPTER 9 TROUBLESHOOTING
9
9.
5
Er
ror C
o
de List
0C65
H
[SP.UNIT LAY ERR.]
Hardware failure inside the Ethernet adapter module was
detected.
■
Supplementary information
• Common information: Module No. (slot No.)
• Individual information: -
■
Diagnostic timing
• When powered on or reset
The hardware of the Ethernet adapter module may be faulty.
Please consult your local Mitsubishi representative.
RUN: Flashing
ERR.: On
0C92
H
[SYSTEM LAY ERR.]
Hardware failure inside the Ethernet adapter module was
detected.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• When powered on or reset
The hardware of the Ethernet adapter module may be faulty.
Please consult your local Mitsubishi representative.
RUN: Flashing
ERR.: On
0FD1
H
[PARAMETER ERROR]
Parameters are corrupted.
■
Supplementary information
• Common information: File name
• Individual information: Parameter No.
■
Diagnostic timing
• When powered on or reset, or when parameters are written
Write the parameters to the Ethernet adapter module again.
If the same error is displayed again, the memory in the
Ethernet adapter module is in failure. Please consult your
local Mitsubishi representative.
RUN: Flashing
ERR.: On
0FD4
H
[PARAMETER ERROR]
The parameter file is incorrect.
Or, the contents of the file are not parameters.
■
Supplementary information
• Common information: File name
• Individual information: Parameter No.
■
Diagnostic timing
• When powered on or reset, or when parameters are written
Check if the type of the parameter file is shown as "***.QPA"
and if the file contains parameters.
RUN: Flashing
ERR.: On
1038
H
[LINK PARA. ERROR]
The network No. of the CC-Link IE Field Network is the same as
the third octet value of the IP address.
Or, parameters are corrupted.
■
Supplementary information
• Common information: File name
• Individual information: Parameter No.
■
Diagnostic timing
• When powered on or reset
Correct the parameters and write them to the Ethernet
adapter module again.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
17A0
H
[WDT ERROR]
The watchdog timer timed out.
■
Supplementary information
• Common information: Time (200ms)
• Individual information: Time (value actually measured)
■
Diagnostic timing
• Any time
Take measures on the power supply system to prevent
momentary power failure, and reset the module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.: On
17A1
H
2AC4
H
[NETWORK ERROR]
A CC-Link IE Field Network error has occurred.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
• Perform the CC-Link IE Field Network diagnostics from the
master station to check the network status. Then take
action to correct the problem.
• Check the network’s error code of the error that occurred at
the same time using the error history of the CC-Link IE
Field Network diagnostics from the master station.
RUN: On
ERR.: On
Error
code
Error and cause
Action