125
CHAPTER 7 COMMUNICATION OF THE ETHERNET ADAPTER MODULE
7
7.
3
IP
Co
mm
uni
ca
tions
over
CC-
Li
nk
I
E
F
ield
Net
w
ork
(I
P
P
a
cket
T
rans
fe
r F
unct
ion)
(1) Test method
1.
Open the "IP Communication Test" dialog box in the configuration tool.
[Online]
[Diagnostics]
[IP Communication Test] button
2.
Enter the IP address of the external device (request destination device) for "Communication
Target".
3.
Click the [Test] button.
●
In the IP communication test, whether IP communications can be performed between the Ethernet adapter module
(request destination) and the external device (request source) set in "Communication Target" is checked using the Ping
command. If the external device does not support the Ping command, the IP communication test ends abnormally.
●
Up to four IP communication tests can be executed at the same time.
●
When the external device (request destination) is connected to a CPU module, the IP communication test cannot be
executed for the external device (request destination). Set the IP address of the CPU module connected to the external
device (request destination) in the "Communication Target" field on the "IP Communication Test" dialog box.
Source where the
IP communication test
was executed
Communications can be checked
using the Ping command.
Communications can be checked
using the Ping command.