33
CHAPTER 3 SPECIFICATIONS
3
3.
2 Per
form
ance Spec
ificat
io
ns
(2) CC-Link IE Field Network part
Item
Specification
Maximum link points per
network
RWw
8192 points, 16KB
RWr
8192 points, 16KB
RX
16384 points, 2KB
RY
16384 points, 2KB
Maximum link points per
station
RWw
1024 points, 2KB
RWr
1024 points, 2KB
RX
2048 points, 256 bytes
RY
2048 points, 256 bytes
Station type
Intelligent device station
Station No.
1 to 120
Network No.
1 to 239
Communication method
Token passing method
Communication speed
1Gbps
Transmission path
Line or star topology (Coexistence of line topology and star topology is possible.), ring topology
Connection cable
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher, (Double shielded/STP), Straight cable (
Maximum station-to-station
distance
Up to 100m (compliant with ANSI/TIA/EIA-568-B (Category 5e)) (
Overall cable distance
Line topology: 12000m (when connecting 1 master station and 120 slave stations)
Star topology: Depends on the system configuration
Ring topology: 12100m (when connecting 1 master station and 120 slave stations)
Number of cascade connections
Up to 20