165
CHAPTER 9 TROUBLESHOOTING
9
9.
5
Er
ror C
o
de List
0310
H
Data length error
• Correct the read or write data length.
• When the read or write data length is too long, divide it into parts for a
command request.
0311
H
Request message error
Retry the transient transmission.
0312
H
Target station No. error
0313
H
Target station No. error
Correct the request command at the transient request source, and retry the
operation.
0314
H
System error
Please consult your local Mitsubishi representative.
0315
H
IP communication test in progress
Retry the IP communication test after a while. (Up to four IP communication
tests can be concurrently executed.)
0316
H
IP communication test execution error (no response to Ping)
• Check "Communication Target" in the "IP Communication Test" dialog
box.
• Check and correct the status of the cable connection and line between
the CC-Link IE Field Network gateway setting station and the
communication destination.
• Enable a response to the Ping command (ICMP echo request) in the
firewall settings on the external device or antivirus software.
0380
H
Request source ID error
Restart the Ethernet adapter module. If the same error is displayed again,
please consult your local Mitsubishi representative.
0381
H
Receive error
When the receiving station encountered overloading of transient data, send
the data from the source after a given time has elapsed.
0382
H
Receive queue full
0383
H
Send error
Reduce the frequency of transient transmission and then retry the
operation.
0384
H
System error
Please consult your local Mitsubishi representative.
0400
H
ASCII conversion error
• Set "Binary Code" in the configuration tool, and restart the Ethernet
adapter module to start communication.
• Correct the data sent from the external device.
• Correct the setting for the subcommand.
• Check the device settings.
0401
H
Word device read/write size error
Correct the number of read or write points, and send the data to the
Ethernet adapter module again.
0402
H
Bit device read/write size error
0403
H
Random read/write bit device size error
0404
H
Random read/write word device size error
0405
H
File size error
Correct the number of read or write points (or bytes), and send the data to
the Ethernet adapter module again.
0406
H
Address range error
Correct the start address or the number of read or write points, and send the
data to the Ethernet adapter module. (Do not exceed the maximum address
number.)
0407
H
Unsupported command
Check and correct the request data.
0408
H
Device name error
Correct the device, and read or write the device again.
0409
H
Unsupported device specified
040A
H
Device access type error
Correct the request data (e.g. the subcommand), and send them to the
Ethernet adapter module again.
040B
H
Unregistered monitoring
Register the monitoring data before start monitoring.
040C
H
Response monitoring timer timeout
• Increase the monitoring timer value.
• Check if the Ethernet adapter module is operating properly.
• Correct the network or station number.
• If a station with another network number is set as the destination, correct
the routing parameter value.
• If a station with another network number is set as the destination, check
the network number for duplication.
• Confirm the IP address. (
040D
H
ACK error
• Correct the network or station number.
• Correct the I/O number of the target module.
• Correct the read or write request data.
040E
H
Request data error
Correct the request data, and send them to the Ethernet adapter module
again.
End code or
error code
Error and cause
Action