167
CHAPTER 9 TROUBLESHOOTING
9
9.
5
Er
ror C
o
de List
(2) Error code list (0800
H
to 2AC4
H
)
The following lists the error messages, error conditions, causes, and actions of the error codes (0800
H
to 17FF
H
).
The "
Supplementary information" in the "Error and cause" column can be confirmed by any of the following.
• Common error information (SD5 to SD15)
• Individual error information (SD16 to SD26)
Error
code
Error and cause
Action
LED status
0800
H
[ADAPTER UNIT DOWN]
The Ethernet adapter module is running away or faulty.
• Malfunction due to noise
• Hardware failure
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Take action against noise, and reset the module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
0801
H
0802
H
0803
H
0804
H
0805
H
0806
H
0809
H
[ADAPTER UNIT DOWN]
The power supply part or the Ethernet adapter module is faulty.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Reset the Ethernet adapter module.
If the same error is displayed again, the Ethernet adapter
module may be faulty. Please consult your local Mitsubishi
representative.
RUN: Flashing
ERR.: On
0823
H
[ADAPTER UNIT DOWN]
The Ethernet adapter module is running away or faulty.
• Malfunction due to noise
• Hardware failure
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Take action against noise, and reset the module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
085A
H
[ADAPTER UNIT DOWN]
The Ethernet adapter module is running away or faulty.
• Malfunction due to noise
• Hardware failure
■
Supplementary information
• Common information: -
• Individual information: Breakdown information
■
Diagnostic timing
• Any time
0865
H
[RAM ERROR]
The RAM built in the Ethernet adapter module is faulty.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• When powered on or reset
Take action against noise, and reset the module.
If this error occurs again, the hardware of the Ethernet
adapter module may be faulty. Please consult your local
Mitsubishi representative.
RUN: Flashing
ERR.: On
0866
H
0867
H
0868
H
08A1
H
[RAM ERROR]
The data in the device memory built in the Ethernet adapter
module were overwritten.
■
Supplementary information
• Common information: -
• Individual information: -
■
Diagnostic timing
• Any time
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......