24
2.2
CC-Link IE Field Network Part
Respective names of the Ethernet adapter module's CC-Link IE Field Network part are shown below.
(1) LEDs
Name
Description
RUN LED
Indicates the operating status.
On: Normally operating. (RUN status)
Flashing: Normally operating. (STOP status)
• The Ethernet adapter module's switch is set to STOP. (Data transfer among the Ethernet adapter module devices is
stopped.)
• The master station is in the STOP status. (Data transfer among the Ethernet adapter module devices is continued.)
• A remote STOP request is being received.
• The Ethernet adapter module stopped due to an error (except a watchdog timer error).
Off: A hardware failure or a watchdog timer error has occurred.
MODE LED
Indicates the mode.
On: Online mode
Flashing: Test mode
Off: Offline mode
D LINK LED
Indicates the data link status of CC-Link IE Field Network.
On: Data link in operation (cyclic transmission in progress)
Flashing: Data link in operation (cyclic transmission stopped)
Off: Data link not in operation (disconnected) or the module is in offline mode.
SD LED
Indicates the data sending status on CC-Link IE Field Network.
On: Data being sent
Off: No data being sent
RD LED
Indicates the data receiving status on CC-Link IE Field Network.
On: Data being received
Off: No data being received
1)
2)
3)
Summary of Contents for NZ2GF-ETB