224
(1) Diagnostic information
Number
Name
Description
Details
Set by
(Set timing)
SD0
Diagnostic
error
Diagnostic
error code
When an error is detected in the diagnostics, an error code is stored.
The data is the same as the latest information in the error history and system error history.
S
(Error)
SD1
Clock time of
diagnostic
error
Clock time of
diagnostic
error
Data of the year (last two digits) and month (2-digit BCD code) when SD0 data were updated
are stored.
The clock of the Ethernet adapter module synchronizes the clock of the master station. (
SD2
Data of the day and hour (2-digit BCD code) when SD0 data were updated are stored.
The clock of the Ethernet adapter module synchronizes the clock of the master station. (
SD3
Data of the minute and second (2-digit BCD code) when SD0 data were updated are stored.
The clock of the Ethernet adapter module synchronizes the clock of the master station. (
SD4
Error
information
category
Error
information
category code
Data are stored in the common information (SD5 to SD15) or individual information (SD16 to
SD26) areas respectively.
A category code that determines what type of error information is stored.
S
(Error)
Any of the following are stored in the common information category codes area.
0: None
1: Module No. (slot No.)
2: File name
3: Time (set value)
Any of the following are stored in the individual information category codes area.
0: None
1: (Empty)
2: None
3: Time (measured value)
4: None
5: Parameter No.
6: None
7: None
8: None
9: Failure information
12: None
13: None
b15
b7
b0
b8
to
to
Year (0 to 99) Month (1 to 12)
(Example) January, 2010
1001
H
b15
b7
b0
b8
to
to
Day (1 to 31) Hour (0 to 23)
(Example) 10 a.m. on 25th
2510
H
b15
b7
b0
b8
to
to
Minutes (0 to 59) Seconds (0 to 59)
(Example) 35 min. 48 sec.
3548
H
b15
b7
b0
b8
to
to
Individual information category codes Common information category codes