226
*1
The extension name is listed below.
(2) System information
SD50
Error clear
Error code to
be cleared
The error code to be cleared is stored.
U
SD53
DC DOWN
detection
DC DOWN
detection
count
Every time the input voltage of the Ethernet adapter module drops to 65% of the rated voltage
(DC power), the stored value is incremented by one.
The counter repeats cycles of 0
32767
-32768
0.
S
(Error)
SD
n
SD
n+1
Extension
name
File type
Upper 8 bits
Lower 8 bits
Upper 8 bits
51
H
50
H
41
H
QPA
Parameter
Number
Name
Description
Details
Set by
(Set timing)
SD200
Switch status
Ethernet
adapter
module switch
status
The switch status of the Ethernet adapter module is stored.
0: RUN
1: STOP/RESET
S
(Switch
change)
SD201
LED status
LED status
The LED status of the Ethernet adapter module is stored.
0: Off
1: On
2: Flashing
1) ERR.
2) D LINK
3) RD
4) SD
5) MODE
6) RUN
(In the offline mode, RD and SD are always off.)
S
(Status
change)
SD203
Operating
status
Operating
status
The operating status of the Ethernet adapter module is stored.
1) Operating status
0: RUN
2: STOP
2) Cause of STOP
The latest cause of the change in the operation status is stored.
0: STOP switch
1: Master station STOP
2: Remote operation from GX Works2, etc.
4: Error
S
(Status
change)
Number
Name
Description
Details
Set by
(Set timing)
b15
b12b11
b8 b7
b4 b3
b0
1)
2)
3)
4)
6)
5)
0
0
0
0
to
to
to
to
b15
b12b11
b8 b7
b4 b3
b0
1)
2)
0
0
0
0
0
0
0
0
to
to
to
to
Summary of Contents for NZ2GF-ETB
Page 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Page 198: ...196 a Detail Setting ...
Page 246: ...244 Memo ...
Page 253: ......