Connection of servo amplifier
Connection
MELSERVO J2-Super
3 - 1
3
Connection
3.1
Connection of servo amplifier
3.1.1
No-fuse circuit breakers, fuses, magnetic contactors and cables
The terminal strips for mains and motor connections become visible after opening the flap on the
front cover (MR-J2S-100B or less) or after removing the front cover (MR-J2S-200B or larger and
MR-J2S-350B4 or larger). Mains power is connected via terminals L1, L2 and L3. In the case of
200V models up to 750W a 1-phase connection is possible.
Connect the motor to the output terminals U, V and W.
For a description of the terminals for the power connections see Tab. 3-4 and Tab. 3-5 on page
3-4.
The following accessories in this section are to be used for the operation of the servo amplifier
and servo motor:
b
CAUTION:
Only the voltage stated may be connected to the relevant terminals. An incorrect
voltage can lead to damage to the servo amplifier.
Servo amplifier
Injection
Dimensions [mm²]
No-fuse ciruit
breaker
Fuse
Magnetic
contactor
L1-L2-L3
L11-L21
U-V-W
Electro-
magnetic
brake
Servo amplifier 200V
MR-J2S-10B
NF30, 5 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-20B
NF30, 5 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-40B
NF30, 10 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-60B
NF30, 15 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-70B
NF30, 15 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-100B
NF30, 15 A
16 A
S-N10
1.5
1.5
2.5
1.5
MR-J2S-200B
NF30, 20 A
20 A
S-N18
2.5–4
1.5
4
1.5
MR-J2S-350B
NF30, 20 A
25 A
S-N20
4–6
1.5
6
1.5
MR-J2S-500B
NF50, 50 A
50 A
S-N35
4–6
1.5
6
1.5
MR-J2S-700B
NF100, 75 A
50 A
S-N50
10
1.5
10
1.5
Servo amplifier 400V
MR-J2S-60B4
NF30, 5 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-100B4
NF30, 10 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-200B4
NF30, 15 A
16 A
S-N10
1.5
1.5
1.5
1.5
MR-J2S-350B4
NF30, 20 A
20 A
S-N18
2.5–4
1.5
4
1.5
MR-J2S-500B4
NF30, 20 A
25 A
S-N20
4–6
1.5
6
1.5
MR-J2S-700B4
NF50, 50 A
50 A
S-N35
4–6
1.5
6
1.5
Tab. 3-1:
Required equipment
Summary of Contents for MELSERVO MRJ2S-B
Page 2: ......
Page 4: ......
Page 6: ......
Page 14: ...VIII ...
Page 18: ...Contents XII ...
Page 48: ...Introduction System configuration 1 30 ...
Page 58: ...Installation General environmental conditions 2 10 ...
Page 86: ...Connection Station number setting 3 28 ...
Page 122: ...Operation Gain 4 36 ...
Page 134: ...Absolute position detection system General description 6 6 ...
Page 146: ...Accessories Special accessories 7 12 ...
Page 148: ...Maintenance and Inspection Life 8 2 ...
Page 174: ...Specifications Standard specifications 10 16 ...
Page 176: ...EMC Directives Requirements 11 2 ...
Page 198: ...Index iv ...
Page 199: ......