Operation
Parameter
4 - 22
Set the parameter value and switch power off once, then switch it on again to make that
parameter setting valid.
Number
Symbol
Initial value
Unit
Setting range
40
BLK
0000
Refer description
Parameter entry prohibition
Depending on the setting, various parameter ranges may be blocked for reading or writing (refer topage 4-11).
Setting
Function
Operation from controller
Operation from
setup-software
0000
(Initial value)
Read
Parameter No. 1 to No. 39
Parameter No. 1 to No. 11
and No. 40
Write
000A
Read
Parameter No. 1 to No. 39
Parameter No. 40
Write
000C
Read
Parameter No. 1 to No. 39
Parameter No. 1 to No. 40
Write
Parameter No. 1 to No. 11
and No. 40
000E
Read
Parameter No. 1 to No. 39
Parameter No. 1 to No. 40
Write
100E
Read
Parameter No. 1 to No. 39
Parameter No. 1 to No. 40
Write
Parameter No. 40
Tab. 4-13:
Parameter list details (9)
Summary of Contents for MELSERVO MRJ2S-B
Page 2: ......
Page 4: ......
Page 6: ......
Page 14: ...VIII ...
Page 18: ...Contents XII ...
Page 48: ...Introduction System configuration 1 30 ...
Page 58: ...Installation General environmental conditions 2 10 ...
Page 86: ...Connection Station number setting 3 28 ...
Page 122: ...Operation Gain 4 36 ...
Page 134: ...Absolute position detection system General description 6 6 ...
Page 146: ...Accessories Special accessories 7 12 ...
Page 148: ...Maintenance and Inspection Life 8 2 ...
Page 174: ...Specifications Standard specifications 10 16 ...
Page 176: ...EMC Directives Requirements 11 2 ...
Page 198: ...Index iv ...
Page 199: ......