General description
Absolute position detection system
MELSERVO J2-Super
6 - 1
6
Absolute position detection system
6.1 General
description
6.1.1 Specifications
Time to hold data by a battery with power off.
Period during which data can be held by the super capacitor in the encoder after power-off,
with the battery voltage low or the battery removed, or during which data can be held with
the encoder cable disconnected. Battery replacement should be finished within this period.
b
CAUTION:
If an absolute position erase alarm (25) has occurred, always perform home position
setting again. Not doing so can cause runaway.
Item
Description
System
Electronic battery backup system
Battery
Lithium battery A6BAT or MR-BAT
Maximum revolution range
Reference position
±
32767 rev.
Maximum speed at power failure
500r/min
Battery backup time
Approx. 10000h
Data holding time during battery replacement
2h at delivery, 1h in 5 years after delivery
Battery storage period
Approx. 5 years
Tab. 6-1:
Specification overview
Summary of Contents for MELSERVO MRJ2S-B
Page 2: ......
Page 4: ......
Page 6: ......
Page 14: ...VIII ...
Page 18: ...Contents XII ...
Page 48: ...Introduction System configuration 1 30 ...
Page 58: ...Installation General environmental conditions 2 10 ...
Page 86: ...Connection Station number setting 3 28 ...
Page 122: ...Operation Gain 4 36 ...
Page 134: ...Absolute position detection system General description 6 6 ...
Page 146: ...Accessories Special accessories 7 12 ...
Page 148: ...Maintenance and Inspection Life 8 2 ...
Page 174: ...Specifications Standard specifications 10 16 ...
Page 176: ...EMC Directives Requirements 11 2 ...
Page 198: ...Index iv ...
Page 199: ......