Connection
Connection of servo amplifier
3 - 4
Main circuit terminal overview for MR-J2S-60B to MR-J2S-700B
Main circuit terminal overview for MR-J2S-60B4 to MR-J2S-700B4
Terminal
Signal
Description
L1, L2, L3 Main circuit power supply The rated voltage range is 3-phase 200 to 230V AC, 50/60 Hz. Up to 750 W
a 1-phase power supply is possible.
L11, L21
Control circuit power
supply
The rated voltage range is 1-phase 200 to 230V AC, 50/60 Hz. Here L11
must be equal in phase to L1 and L21 equal in phase to L2.
N
Brake unit option
When using the optional brake unit, connect it across the terminals P and N.
Before connecting the optional brake unit, you must disconnect the internal
brake resistor across the terminals P and C.
Do not connect a optional brake unit to the servo amplifier of MR-J2S-350B
or less.
P, C, D
Regenerative brake
option/brake unit
MR-J2S-350B or less
The terminals P and D are factory-connected. When connecting an optional
regenerative brake, always disconnect the cable connection across P and D.
Connect the optional regenerative brake across the terminals P and C.
Do not connect a optional brake unit to the servo amplifier of MR-J2S-350B
or less.
MR-J2S-500B or more
When connecting an optional regenerative brake or brake unit, always
disconnect the cable connection across P and C of the internal brake
resistor.
Connect the optional regenerative brake across the terminals P and C.
When using the optional brake unit, connect it across the terminals P and N.
U, V, W
Servo motor output
Connect to the servo motor power supply terminals U, V, W.
PE
Protective earth
Connect this terminal to the protective earth (PE) terminals of the servo
motor and control box for grounding.
Tab. 3-4:
Signal overview (MR-J2S-60B to MR-J2S-700B)
Terminal
Signal
Description
L1, L2, L3 Main circuit power supply The rated voltage range is 3-phase 380 to 480V AC, 50/60Hz.
24V/L11,
0V/L21
Control circuit power
supply
Connect a 24VDC source here. Make sure that the plus pole of the DC
source is connected to terminal 24V/L11 and the minus pole of the DC
source to terminal 0V/L21.
N
Brake unit option
When using the optional brake unit, connect it across the terminals P and N.
Before connecting the optional brake unit, you must disconnect the internal
brake resistor across the terminals P and C.
Do not connect a optional brake unit to the servo amplifier of MR-J2S-200B4
or less.
P, C, D
Regenerative brake
option/brake unit
MR-J2S-200B4 or less
The terminals P and D are factory-connected. When connecting an optional
regenerative brake, always disconnect the cable connection across P and D.
Connect the optional regenerative brake across the terminals P and C.
Do not connect a optional brake unit to the servo amplifier of MR-J2S-200B4
or less.
MR-J2S-350B4 or more
When connecting an optional regenerative brake or brake unit, always
disconnect the cable connection across P and C of the internal brake
resistor.
Connect the optional regenerative brake across the terminals P and C.
When using the optional brake unit, connect it across the terminals P and N.
U, V, W
Servo motor output
Connect to the servo motor power supply terminals U, V, W.
PE
Protective earth
Connect this terminal to the protective earth (PE) terminals of the servo
motor and control box for grounding.
Tab. 3-5:
Signal overview (MR-J2S-60B4 to MR-J2S-700B4)
Summary of Contents for MELSERVO MRJ2S-B
Page 2: ......
Page 4: ......
Page 6: ......
Page 14: ...VIII ...
Page 18: ...Contents XII ...
Page 48: ...Introduction System configuration 1 30 ...
Page 58: ...Installation General environmental conditions 2 10 ...
Page 86: ...Connection Station number setting 3 28 ...
Page 122: ...Operation Gain 4 36 ...
Page 134: ...Absolute position detection system General description 6 6 ...
Page 146: ...Accessories Special accessories 7 12 ...
Page 148: ...Maintenance and Inspection Life 8 2 ...
Page 174: ...Specifications Standard specifications 10 16 ...
Page 176: ...EMC Directives Requirements 11 2 ...
Page 198: ...Index iv ...
Page 199: ......