7. Servo Parameters
7.3 MDS-C1-Vx Standard Specification (MDS-B-Vx Compatible)
II - 178
No. Items
Details
Setting
range
2232 SV032
TOF
Torque
offset
Set the unbalance torque of vertical axis and inclined
axis.
-100 to 100
(Stall [rated]
current %)
2233 SV033
SSF2
Servo
function
selection 2
F E D C B A 9 8
dos
hvx
svx
7 6 5 4 3 2 1 0
fhz2 nfd
zck
bit
Meaning when "0" is set
Meaning when "1" is set
0 zck
Z phase check valid (Alarm 42)
Z phase check invalid
1 nfd1
Set the filter depth for Notch filter 1 (SV038).
2
Value
000
001
010
011
100 101 110
111
3
Depth
(dB)
Infntly
deep
-18.1
-12.0
-8.5
-6.0 -4.1 -2.5
-1.2
Deep
Å
Æ
Shallow
4
Set the operation frequency of Notch filter 2.
5
0: Invalid
3: 750Hz
6: 375Hz
6
1: 2250Hz
4: 563Hz
7: 321Hz
7
fhz2
2: 1125Hz
5: 450Hz
8 to F: 281Hz
8 svx
9 hvx
Set the performance mode of the servo control. (Only for
MDS-C1-Vx)
00: By current loop gain
01: MDS-B-Vx compatible mode selected
10: High gain mode selected
11: High gain mode selected
A
B
C
Digital signal output selection
D
dos
0 :
MP scale absolute position detection, offset demand
signal output
E
1 :
Specified speed signal output
F
2 to F :
Setting prohibited
(Note) Set to "0" for bits with no particular description.
Summary of Contents for MELDAS 60 Series
Page 1: ......
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 13: ...I EXPLANATION OF ALARMS ...
Page 14: ......
Page 95: ...II EXPLANATION OF PARAMETERS ...
Page 96: ......
Page 443: ......