159
Monitor display and monitor output signal
4.12.5 How to calibrate the terminal FM when using the operation panel
Perform the following procedure to calibrate terminal FM using the operation panel FR-DU07.
for
the details of parameters.
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
(When
Pr. 54
= 1)
2.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Press
to read the present set value.
"
" (initial value) appears.
5.
Turn
to change it to the setting value of
" ".
6.
Press
to
set.
Flicker...Parameter setting complete!!
7.
Turn
until
appears.
8.
Press
to
display
.
9.
Turn
until
appears.
Set to
C0 FM terminal calibration.
10.
Press
to enable setting.
11.
If the inverter is at a stop, press the
key
to start the inverter.
(Motor needs not be connected.)
12.
Turn
to adjust the indicator needle to
the desired position.
Analog indicator
13.
Press
.
Setting is complete.
Flicker...Parameter setting complete!!
Turn
to read another parameter.
Press
to return to the
indication (step 8).
Press
twice to show the next parameter (
).
C0 to C7 settings
are enabled.
The monitor set to
Pr. 54
FM terminal function selection
is displayed.
Hz
A