199
Misoperation prevention and parameter setting restriction
(2) Password lock/unlock (
Pr. 296, Pr. 297
)
<Lock>
1) Set parameter reading/writing restriction level.(
Pr. 296
9999)
* During [
Pr. 296
= "101 to 106"], if password unlock error has occurred 5 times, correct password will not unlock the
restriction. All parameter clear can unlock the restriction.
(In this case, parameter settings are cleared.)
2) Write a four-digit number (1000 to 9998) in
Pr. 297
as a password.
(When
Pr. 296
= "9999",
Pr. 297
cannot be written.)
When the password is registered, parameter reading/writing is restricted with the restriction set level in
Pr. 296
until
unlocking.
<Unlock>
There are two ways of unlocking the password.
Enter a password in
Pr. 297
.
Unlocked when a password is correct. If a password is incorrect, an error occurs and not unlocked.
During [
Pr. 296
= "101 to 106"], if password unlock error has occurred 5 times, correct password will not unlock the
restriction. (During password lock)
Perform all parameter clear.
Password lock is unlocked. However, other parameter settings are also cleared.
(3) Parameter operation during password lock/unlock
Reading/writing is unavailable when there is restriction to reading by the
Pr. 160
setting.
Unavailable during the operation.
Correct password will not unlock the restriction.
Pr. 296
Setting
Value
Restriction of Password
Unlock Error
Pr. 297
Display
1 to 6
No restriction
Always 0
101 to 106
Restricted at fifth error
Displays error count
(0 to 5)
REMARKS
After registering a password, a read value of
Pr. 297
is always "0" to "5".
When a password restricted parameter is read/written,
is displayed.
Even if a password is registered, parameters which the inverter itself writes, such as inverter parts life, are overwritten as
needed.
Even if a password is registered,
Pr. 991
PU contrast adjustment
can be read/written when a parameter unit (FR-PU04/FR-PU07)
is connected.
NOTE
If the password has been forgotten, perform all parameter clear to unlock the parameter restriction. In that case,
other parameters are also cleared.
All parameter clear cannot be performed during the operation.
Do not use FR Configurator under the conditions that parameter read is restricted (
Pr. 296
= "4, 5, 104, 105").
FR Configurator may not function properly.
Parameter operation
Unlocked
Password registered
Locked
Pr. 296
= 9999
Pr. 297
= 9999
Pr. 296
9999
Pr. 297
= 9999
Pr. 296
9999
Pr. 297
= 0 to 4
(Read value)
Pr. 296
= 101 to 106
Pr. 297
= 5
(Read value)
Pr. 296
Read
Write
Pr. 297
Read
Write
Performing parameter clear
Performing parameter all clear
Performing parameter copy
: enabled,
: restricted
REMARKS
When
Pr. 296
= "4, 5, 104, 105" and using the parameter unit (FR-PU04/FR-PU07), PUJOG operation is unavailable.
When writing is restricted from PU mode operation command (
Pr. 296
= 1, 2, 4, 5, 101, 102, 104, 105), switching of operation
mode by easy setting mode is unavailable. (
During password lock, parameter copy of the parameter unit (FR-PU07) cannot be performed.
Parameters referred to
Pr. 77 Parameter write selection
Pr. 160 Extended function display selection
Pr. 551 PU mode operation command source selection