Selection and protection of a motor
4.9.2
Applied motor (Pr. 71, Pr. 450)
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Performing IPM parameter initialization changes the settings.
....Specifications differ according to the date assembled.
to check the SERIAL number.
(1) Set the motor to be used
Refer to the following list and set the parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required when using a constant-torque motor or IPM motor. Thermal characteristic of the electronic thermal
relay function suitable for the motor is set.
When General-purpose magnetic flux vector is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
etc.) necessary for control are selected as well.
Parameter
Number
Name
Initial
Value
Setting Range
Description
71
Applied motor
0
0, 1, 3, 13,
23, 40, 43, 50, 53,
120, 210
Selecting the standard motor, constant-torque
motor, or IPM motor sets the corresponding
motor thermal characteristic.
450
Second applied motor
9999
0, 1
Set when using the second motor.
9999
Second motor is invalid.
(Thermal characteristic of the first motor
(
Pr. 71
))
Pr. 71 (Pr. 450)
Setting
Used motor
Thermal Characteristic of the
Electronic Thermal Relay Function
Pr. 71
Pr. 450
Standard
Constant-
torque
IPM
0
(
Pr. 71
initial value)
Standard motor (such as SF-JR)
1
Mitsubishi constant-torque motor (such as SF-JRCA)
40
—
Mitsubishi high-efficiency motor (SF-HR)
50
—
Mitsubishi constant-torque motor (SF-HRCA)
3
—
Standard motor
Select "offline auto tuning
setting"
13
—
Constant-torque motor
23
—
Mitsubishi standard motor(SF-JR 4P 1.5kW or less)
43
—
Mitsubishi high-efficiency motor (SF-HR)
53
—
Mitsubishi constant-torque motor(SF-HRCA)
120
—
High-efficiency IPM motor (MM-EF)
210
—
Premium high-efficiency IPM motor MM-EFS
—
9999
(initial
value)
Without second applied motor
Performing IPM parameter initialization changes the settings.
REMARKS
When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in
Pr. 71
.
(Refer to
page
for offline auto tuning.)
For the 5.5K and 7.5K, the
Pr. 0
Torque boost
and
Pr. 12 DC injection brake operation voltage
settings are automatically changed
according to the
Pr. 71
setting as follows. (These are not automatically changed by the
Pr.998
IPM parameter initialization
setting.)
NOTE
Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when using a
geared motor (GM-S, GM-D, GM-SY, GM-HY2 series) to perform General-purpose magnetic flux vector control.
V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC
Automatic Change
Parameter
Standard Motor
Setting
Constant-torque Motor
Setting
Pr. 0
3%
2%
Pr. 12
4%
2%
Pr. 71
setting: 0, 3, 23, 40, 43, 120, 210
Pr. 71
setting: 1, 13, 50, 53