IPM motor control <IPM>
4.3.2
Initializing the parameters required to drive an IPM motor (Pr.998)
<
IPM>
....Specifications differ according to the date assembled.
to check the SERIAL number.
(1)
IPM parameter initialization (Pr.998)
By performing IPM parameter initialization, initial settings required to drive an IPM motor can be set in parameters.
When
Pr. 998
= "1, or 12" the monitor is displayed and the frequency is set using the motor rotations per minute.
To use frequency to display or set, set
Pr. 998
= "101 or 112."
Set
Pr. 998
= "0" to change the parameter settings from the settings required to drive an IPM motor to the settings
required to drive a general-purpose motor.
Parameters referred to
Pr.60 Energy saving control selection
Pr.72 PWM frequency selection
Pr.190 or Pr.192 (Output terminal function selection)
Pr. 261 Power failure stop selection
Pr.653 Speed smoothing control
Pr.800 Control method selection
By performing IPM parameter initialization, IPM motor control is selected and the parameters, which are
required to drive an IPM motor, are changed. Initial settings and setting ranges of the parameters are adjusted
automatically to drive an IPM motor.
Initialization is performed by setting
Pr.998 IPM parameter initialization
or by choosing the mode on the operation
panel.
Parameter
Number
Name
Initial
value
Setting
range
Description
998
IPM parameter
initialization
0
0
Parameter settings for a general-
purpose motor (frequency)
Initial parameter
settings required to
drive a general-purpose
motor are set.
1
Parameter settings for a high-efficiency
IPM motor MM-EF
(rotations per minute)
Initial parameter
settings required to
drive an IPM motor are
set.
12
Parameter settings for a premium high-
efficiency IPM motor MM-EFS
(rotations per minute)
101
Parameter settings for a high-efficiency
IPM motor MM-EF
(frequency)
112
Parameter settings for a premium high-
efficiency IPM motor MM-EFS
(frequency)
Pr.998
Setting
Description
Operation in the parameter setting
mode of the operation panel
0
Parameter settings for a general-purpose motor (frequency)
"
(IPM)"
Write "0"
1
Parameter settings for a high-efficiency IPM motor MM-EF
(rotations per minute)
"
(IPM)"
Write "1"
12
Parameter settings for a premium high-efficiency IPM motor MM-
EFS (rotations per minute)
"
(IPM)"
Write "12"
101
Parameter settings for a high-efficiency IPM motor MM-EF
(frequency)
Invalid
112
Parameter settings for a premium high-efficiency IPM motor MM-
EFS (frequency)
Invalid
REMARKS
Make sure to set
Pr.998
before setting other parameters. If the
Pr.998
setting is changed after setting other parameters, some of
those parameters will be initialized too. (Refer to "(2) IPM parameter initialization list" for the parameters that are initialized.)
To change back to the parameter settings required to drive a general-purpose motor, perform parameter clear or all parameter
clear.
If the setting of
Pr.998 IPM parameter initialization
is changed from "1, 12 (rotations per minute)" to "101, 112 (frequency)," or
from "101, 112" to "1, 12," all the target parameters are initialized.
The purpose of
Pr.998
is not to change the display units. Use
Pr.144
Speed setting switchover
to change the display units between
rotations per minute and frequency.
Pr.144
enables switching of display units between rotations per minute and frequency
without initializing the parameter settings.
Example) Changing the
Pr.144
setting between "6" and "106" switches the display units between frequency and rotations per
minute.
IPM
IPM
IPM