88
IPM motor control <IPM>
4.3.3
IPM motor test operation (Pr.800)
<IPM>
The above parameters can be set when
Pr.160 User group read selection
= "0."
(1) Test operation
To activate the IPM motor test operation, set
Pr.998 IPM parameter initialization
, change the control to IPM motor
control, then set
Pr.800 Control method selection
= "9."
Perform a test operation by giving a frequency and a start command under each of PU/External/Network operation
mode.
Without connecting an IPM motor, the frequency movement can be checked by the monitor or analog signal
output.
Two types of operation can be selected using this parameter: an actual operation by connecting an IPM motor, or
a test operation without connecting an IPM motor to simulate a virtual operation.
Parameter
Number
Name
Initial
value
Setting
range
Operation
800
Control method selection
30
9
IPM motor test operation (Motor is not driven even if it is
connected.)
30
Normal operation (Motor can be driven.)
REMARKS
In the test operation, current is not detected and voltage is not output. Related monitor displays of the output current
and voltage show "0."
IPM
IPM
IPM
Time
Running frequency
(FM output)
STF
RUN