279
Setting the parameter unit and operation panel
(2) Using the setting dial like a potentiometer to set the frequency
Operation example Change the frequency from 0Hz to 60Hz during operation
Operation Display
1. Screen at power-ON
The monitor display appears.
2.
Press
to choose the PU operation mode.
PU indicator is lit.
3.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously
appears.)
4.
Turn
until
(Pr. 160)
appears.
5.
Press
to read the present set value.
"
"(initial value) appears.
6.
Turn
to change it to the set value "
".
7.
Press
to set.
Flicker
···
Parameter setting complete!!
8.
Change
Pr. 161
to the setting value of "
"
in the similar manner. (Refer to step 4 to 7.)
Flicker
···
Parameter setting complete!!
9.
Mode/monitor check
Press
twice to choose the monitor/
frequency monitor.
10.
Press
to start the inverter.
11.
Turn
until "
" appears.
The flickering frequency is the set frequency.
You need not press
.
The frequency flickers for about 5s.
REMARKS
If the display changes from flickering "60.00" to "0.00", the setting of
Pr. 161 Frequency setting/key lock operation selection
may not
be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by merely turning the dial.
When the frequency is changed, it will be stored in EEPROM as the set frequency after 10s.
NOTE
When using the setting dial under general-purpose motor control, the frequency goes up to the set value of
Pr.1
Maximum frequency
(initial value:120Hz). When using the setting dial under IPM motor control, the frequency goes up
to the set value of the maximum motor speed (frequency).
Adjust the setting of
Pr.1 Maximum frequency
according to the application.