142
Function assignment of external terminal and control
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN signal)
When the inverter is ready to operate, the output of the operation ready signal (RY) is ON. (It is also ON during inverter running.)
When the inverter's output frequency reaches
Pr. 13
Starting frequency
(0.01Hz under IPM motor control) or higher, the
inverter running signal (RUN) is output. During an inverter stop or DC injection brake operation, the output is OFF.
When using the RY and RUN signals, assign functions to
Pr.190 or Pr.192 (output terminal selection function)
referring to the
table below.
Output
Signal
Pr. 190
and
Pr. 192
Setting
Positive logic
Negative logic
RY
11
111
RUN
0
100
Inverter
Status
Start
Signal
OFF
(during
stop)
Start
Signal ON
(during
stop)
Start
Signal ON
(during
operation)
Under DC
Injection Brake
Output Shutoff
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Output
signal
Start
signal
ON
Start
signal
OFF
RY
ON
ON
ON
ON
OFF
ON
ON
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
This signal turns OFF during power failure or undervoltage.
Output is shutoff in conditions like a fault and when the MRS signal is ON.
REMARKS
The RUN signal (positive logic) is assigned to the terminal RUN in the initial setting.
During IPM motor control, the RUN signal is output about 100ms after turning ON the start command (STF, STR). The delay is
due to the magnetic pole detection.
Time
Power supply
Output frequency
STF
RH
RY
Pr. 13 Starting frequency
ON
OFF
ON
OFF
ON
OFF
ON
DC injection brake operation point
DC injection brake operation
RUN
ON
OFF
Reset processing