Monitor display and monitor output signal
4.12 Monitor display and monitor output signal
4.12.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505)
The above parameter can be set when
Pr. 160 Extended function display selection
= "0".
Performing IPM parameter initialization sets back the settings to the initial settings. (
)
Performing IPM parameter initialization changes the settings. (
The maximum value of the setting range differs according to the
Pr. 1 Maximum frequency (Pr. 18 High speed maximum frequency)
,
and it can be calculated from
the following formula.
Note that the maximum setting value of
Pr. 37
is 9998 if the result of the above formula exceeds 9998.
If
Pr. 999 Automatic parameter setting
setting is set to "20" or "21" while the machine speed is displayed (
Pr.37
0), calculate the rotations per minute based on
the changed
Pr.505
setting, and set
Pr.37
again.
(
To display a machine speed, set
Pr.37
to the machine speed at the frequency set in
Pr. 505
, and set
Pr. 144
to the number of
motor poles (2, 4, 6, 8, 10).
For example, when
Pr. 505
= "60Hz" and
Pr. 37
= "1000", "1000" is displayed on the machine speed monitor at the running
frequency of 60Hz. When running frequency is 30Hz, "500" is displayed.
When displaying the motor speed, set the number of motor poles + 100 (102, 104, 106, 108, 110) to
Pr. 144
.
When both
Pr. 37
and
Pr. 144
have been set, their priorities are as given below.
Pr. 144
, 102 to 110
Pr. 37
, 1 to 9998
Pr. 144
, 2 to 10
A combination of the
Pr.37
and
Pr. 144
settings determines the monitored item and the setting increment as shown in the
table below. (Initial settings are outlined with bold borders)
Purpose
Parameter that should be Set
Refer to
Page
Display motor speed
Set speed
Speed display and speed setting
Pr. 37, Pr. 144, Pr. 505
Change PU monitor display data
Monitor display/PU main display
data selection
Cumulative monitor clear
Pr. 52, Pr. 54, Pr. 170, Pr. 171,
Pr. 268, Pr. 563, Pr. 564, Pr. 891
Change the monitor output from
terminal FM
Terminal FM function selection
Pr. 54
Set the reference of the monitor
output from terminal FM
Terminal FM standard setting
Pr. 55, Pr. 56
Adjust terminal FM outputs
Terminal FM calibration
Pr. 900
The monitor display and frequency setting of the PU (FR-PU04/FR-PU07) can be changed to the machine speed.
Parameter
Number
Name
Initial
Value
Setting Range
Description
37
Speed display
0
0
Frequency display, setting
0.01 to 9998
Set the machine speed at
Pr.505.
144
Speed setting switchover
4
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
Set the number of motor poles when displaying the motor
speed.
505
Speed setting reference
60Hz
1 to 120Hz
Set the reference speed for
Pr. 37
.
Maximum setting value of
Pr. 37
<
16777.215
60 (Hz)
Setting value of
Pr. 1 (Pr. 18)
(Hz)
Pr. 37
Setting
Pr. 144
Setting
Output Frequency
Monitor
Set Frequency
Monitor
Running Speed
Monitor
Parameter Setting
0
(initial
value)
2 to 10
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
102 to 110
1 r/min
1 r/min
1 r/min
1 r/min
0.01
to 9998
2 to 10
0.001 (Machine speed
0.001 (Machine speed
0.001 (Machine speed
0.01 Hz
102 to 110
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
*1
Motor speed r/min conversion formula............ frequency
120/number of motor poles (
Pr. 144
)
Machine speed conversion formula
................... Pr. 37
frequency/
Pr. 505
setting (Hz)
For
Pr. 144
in the above formula, the value is "
Pr. 144
-100" when "102 to 110" is set in
Pr. 144
and the value is "4" when
Pr. 37
= 0 and
Pr. 144
= 0.
Pr. 505
is always set as frequency (Hz).