Programming—IFC-1010/2020 Programming
Table 25: Page Module
Type ID
Display Label
Type of Device
MPAG
MONITOR PAGE
M50xMJ Monitor Module, M30xMJ, XPM-8, or
XP5-M circuit
dedicated to a normally open switch.
Activation of a module with software type MPAG
connects the remotely located Fire Fighters
Telephone handset to the paging system. This
Type ID is used in conjunction with the PAGE Type
ID (RPJ-1 required).
Table 26: Annunciator Manual
Type ID
Display Label
Type of Device
AMAN
ANN MANUAL
Annunciator Point
that indicates manual mode for
an annunciator module. The annunciator point can
also turn the Manual mode Off or On. This Type ID
is used in conjunction with INA ACS or FACP
shadow point programming.