34
Programming—IFC-1010/2020 Programming
The SCS-8 and SCS-8L annunciator firmware has been updated in
conjunction with Release Merge M2.8 software. The new SCS firmware is
not backward compatible with older revisions of IFC-1010/2020 software.
Prog
!
1
#
3
*
8
????
Level 2 Password
sec1183a
Figure 26: Key Sequence to Change External Interface Parameters
This option allows the programmer to change the parameters associated
with the external interface port. The following example illustrates enabling
all associated parameters.
PRESS 1=INSTL,2=ANN,3=XINT,4=DACT : 3
DO YOU WANT TO CHANGE THE ACS PORT UPLOAD/DOWNLOAD? (Y=YES,N=NO) : Y
DO YOU WANT THE ACS PORT UPLOAD/DOWNLOAD ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE INTELLIGENT SIB ADDRESS? (Y=YES,N=NO) : Y
*ENTER THE INTELLIGENT SIB ADDRESS (0 - 255) : 249
*DO YOU WANT TO CHANGE THE MIB-W THRESHOLD FOR CHANNEL A?(Y=YES,N=NO) : Y
*ENTER THE MIB-W VALUE THRESHOLD FOR CHANNEL A (H=HIGH,L=LOW) : L
*DO YOU WANT TO CHANGE THE MIB-W THRESHOLD FOR CHANNEL B? (Y=YES,N=NO): Y
*ENTER THE MIB-W VALUE THRESHOLD FOR CHANNEL B (H=HIGH,L=LOW) : H
*DO YOU WANT TO CHANGE MIB DATA PORT USAGE? (Y=YES,N=NO) : Y
*DO YOU WANT TO USE BOTH MIB DATA PORTS? (Y=YES,N=NO) : Y
* These items are Fire Network
specific functions and are programmed
only when a SIB-NET is used.
N29
Notes: Node Addresses 249-255 are reserved for diagnostics and should
not
be used.
During an upload/download, the fire protection capability of the
IFC-1010/2020 is enabled (it is limited for download). To reduce
the risk of incompatible databases, the programmer should never
program any parameters into the control panel while an
upload/download is in progress.
To communicate over the external interface, the annunciator
modules must first be disconnected since both functions use the
same serial port.
N4
3=XINT -
External
Interface
Parameters