Programming—IFC-1010/2020 Programming
79
Table 12: Alarm Initiation Modules
Type ID
Display Label
Type of Device
MON
MONITOR
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit used to monitor
normally open
contact, shorting-type devices other than four-wire smoke
detectors (such as conventional heat detectors and pull stations).
MPUL
MON PULL STA
BGX-101L Addressable Manual Pull Station.
NCMN
MON NORM CLD
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit used to monitor
normally closed
contact, opening-type devices.
NOA
NON ALARM
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit that functions
identically to Software Type ID NONA with one exception - subsequent alarms
from this type will not reactivate silenced output devices. Once silenced,
outputs will remain silenced until reactivated by another software type
(or cleared by System Reset and reactivated).
NONA
NON ALM MON
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit used to monitor
normally-open contact, shorting-type non-alarm devices. Activation of a
module with Software Type ID NONA will not initiate a fire alarm condition.
The following conditions will exist:
•
System Alarm LED will not illuminate.
•
Does not activate alarm status line count on a CRT.
•
No effect on modules programmed as APND (alarm pending) or GPND
(general event pending).
•
Alarm, clear alarm, or acknowledgments are not reported for this type.
PULL
PULL STATION
BG-10L Addressable Manual Pull Station
N26
SCON
SMOKE (CONV)
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M used with conventional
four-wire smoke detectors or M502MJ module used to power and monitor
conventional two-wire smoke detectors that are compatibility listed in the
Device Compatibility Technical
Bulletin (LIT-445180)
in the
Fire Management
Accessories Manual.
This module Type ID has a longer reset period than
modules programmed with a Type ID of MON.
WAT
WATER FLOW
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit dedicated to a
Water Flow Alarm device.
Group 4