Programming—IFC-1010/2020 Programming
103
Note
Number
(Cont.)
Section
Note
N21
Pre-Alarm
Function
Pre-Alarm Function is available with Release Merge M2.8 firmware.
N22
Additional
System
Parameters:
Modem
This option must be employed when the keyboard is to be left connected to the
CRT, unless the control panel is the Primary Supervising Station of a Proprietary
Fire Alarm System.
N23
Alter Status
Menu
Group Zone
Disable:
7=GZON
This option is available only with Release Merge M2.8 firmware.
N24
SDEL
This example uses the same SLC addresses and zone as shown in Figure 76.
Only the equation of L1M2 has been changed.
N25
Supported
Products
Addressable detector and module product IDs referenced in this document have
changed with the introduction of Flashscan™ based (300 Series) addressable
devices. Where old 500 Series product IDs are listed in this document, the
following new 300 Series product IDs can be substituted.
500 Series Product ID
300 Series Product ID
1551J/1251J
1351J
2551J/2251J
2351J
2551THJ
2351TJ
DH502+2551J
DH300P
DH500+2551J
DH300RP
5551J
5351J
5551JR
5351R
M500MJ
M300MJ
M501MJ
M301MJ
M502MJ
M302MJ
None
M300SMJ
JBGX-101L
JBG-12LX
M510CJ
M300CJ for NAC
M510CJ (tabs broken)
M300CJ for Form-C Relay
N26
Group 4
Do not use PULL Software Type ID for the model BGX-101L or JBG-12LX Pull
Station. Use this Software Type ID only with the BG-10L, which is no longer
manufactured.
N27
Note 27: System
Scanning Order
Refer to
Note 27:
System Scanning Order
following this table.
N28
External
Equipment:
6=EXTEQ
Bidirectional copy must be enabled when using the CCM-1 board.
N29
3=XINT -
External
Interface
Parameters
Full System
Programming:
2=FSYS
In the XINT menu, the
Enter the Intelligent SIB Address (0-255)
command is used also to get the N2 address of the SIB-N2 or SIB-NET board.
N30
NAM
The NAM-232 is
not
supported by the Metasys Fire Network.
N31
Partial Point
Programming:
3=PPRG
Requires Release Merge M2.8 firmware, otherwise only two SLCs are supported
in the IFC-1010.