Programming—IFC-1010/2020 Programming
77
Table 10: Output Modules
Type ID
Display Label
Type of Device
APND
ALARMS PEND
M5x0CJ Control Module or an XPC-8 circuit
that activates upon receipt of an
alarm condition and remains in the On state until all alarms are Acknowledged.
DACT
DACT CONNECT
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) that delays the reporting of AC power loss. Any other
trouble condition is reported immediately. This module is used in conjunction
with a digital alarm communicator.
GAC
GN ALRM FORC
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) to switch power to a Reverse Polarity Trip Device for
NFPA 72-1993 Remote Station Fire Alarm Systems applications (RPT-680
required).
This type also can be used for general alarm activation.
GAS
GN ALARM
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured as a Municipal Box Transmitter for NFPA 72-1993 Auxiliary Fire
Alarm Systems applications (MBT-1 required).
This type also can be used
for general alarm activation.
GPND
GENERAL PEND
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
that activates upon receipt of an alarm and/or trouble condition, and remains
in the On state until all events are Acknowledged.
GTC
GN TRBL FORC
M5x0CJ Control Module configured as a Form-C relay M300RJ, XPR-8, or
XP5-C (in Relay mode) activated under any System Trouble condition.
PAGE
PAGE
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured for remote paging (RPJ-1 required).
PWRC
POWER (CONV)
M5x0CJ Control Module
configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) used to momentarily interrupt power (during system
reset) to conventional four-wire smoke detectors powered from a remote main
power supply.
SSC
GN SUPR FORC
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) activated under any Supervisory condition (includes
sprinkler type).
TELE
TELEPHONE
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured for telephone operation.
Note:
The M5x0CJ will not provide a ring-back signal when a call is
placed.
TPND
TRBLS PEND
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
that activates upon receipt of a trouble condition, and remains in the On state
until all troubles are Acknowledged.
TRC
TROUBLE FORC
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) that activates upon receipt of trouble conditions and
remains in the On state until the troubles clear.
TRS
TROUBLE
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
that activates upon receipt of a trouble condition and remains in the On state
until the troubles clear.
WFC
GN WAT FORC
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode) activated under any Water Flow condition.
WFS
GN WATER FLW
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) activated
under any Water Flow alarm condition.
Group 2