Programming—IFC-1010/2020 Programming
The following list applies to the output modules listed in Table 10:
•
These software types cannot be programmed for Signal Silence.
•
These software types do not have any CBE programming.
•
The two tabs on the M5x0CJ must not be broken for these software
types unless they are Form-C relay type devices.
Table 11: Software Zones
Type ID
Display Label
Type of Device
FZON
FORWARD ZONE
A software-defined zone that is
forward activating
.
RZON
REVERSE ZONE
A software-defined zone that is
reverse activating
.
The following list applies to the software zones listed in Table 11:
•
A forward activating zone is a software zone in control panel memory,
which, once activated by an input device or other forward zone, may in
turn activate other zones and/or output devices directly. Zones and
output devices activated by a forward zone are contained in the CBE
List of that forward zone.
•
A reverse activating zone is a software zone in control panel memory,
which, if not activated directly by an input device or forward zone,
may be activated through an associated CBE equation. A reverse zone
may be referenced in other CBE equations.
Group 3