66
Programming—IFC-1010/2020 Programming
????
Level 1 Password
alter3.cdr
#
3
Figure 58: Key Sequence to Option 3 (Detector Sensitivity)
Option 3 from the Alter Status menu allows the programmer to alter the
sensitivity of any addressable detector. The sensitivity of a detector can be
set at one of three levels - low, medium, and high
.
N9
The following example illustrates setting a high sensitivity for Detector 14
on SLC 3.
PRESS 1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK : 3
ENTER LXXDYY FOR DETECTOR TO CHANGE (BCKSPC TO ABORT) : L3D14
ENTER THE DETECTOR SENSITIVITY SELECTION FOR THIS DEVICE(L=LOW,M=MED,H=HIGH):H
????
Level 1 Password
alter4.cdr
$
4
Figure 59: Key Sequence to Option 4 (Time)
Option 4 from the Alter Status menu allows the programmer to reset the
time/date system clock.
PRESS 1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK : 4
ENTER THE MONTH (1 - 12)
: 3
ENTER THE DAY-OF-MONTH (1 - 31) : 1
ENTER THE YEAR (0 - 99) : 93
ENTER THE DAY-OF-WEEK (1=SUN,...,7=SAT) : 2
ENTER THE HOURS IN MILITARY TIME (0 - 23) : 15
ENTER THE MINUTES (0 - 59) : 37
JOHNSON CONTROLS ALL SYSTEMS NORMAL 03:37P 03/01/97
Detector
Sensitivity
3=DSEN
Time
4=TIME