70
Programming—IFC-1010/2020 Programming
Notes:
•
Upon completion of the Walk Test LIB selection, a system trouble is
generated to indicate the control panel is operating under limited fire
protection. Only the LIBs selected for Walk Test are affected.
•
Each LIB collects information immediately after it is selected. The
programmer should not generate a Walk Test report until 20 seconds
after LIB selection or the report will be missing data and should be
considered invalid. If this happens, abort the Walk Test and start again.
•
If one or more LIBs have been selected for Walk Test, additional LIBs
cannot be selected without exiting Walk Test.
•
For every device activated during Walk Test, a Walk Test count
message is sent to the printer.
•
Conventional devices attached to an addressable SLC monitoring
device with a Software Type ID of SCON (or equivalent) cannot be
individually tested with Walk Test, because Walk Test does not
perform a reset on associated SLC control devices with a Software
Type ID of PWRC (or equivalent) devices.
IMPORTANT:
Do not perform a System Reset during a Walk Test.
System Reset does not function properly while in
Walk Test mode of operation and may result in
unwanted activation of various output modules. If a
System Reset occurs during a Walk Test, exit Walk
Test mode and re-enter.
Walk Test automatically aborts if no devices are tested for 15 minutes.
Alter623.cdr
^
6
@
2
#
3
$
4
%
5
Or
Figure 65: Key Sequence to Access Device Reports
Walk Test
Reports