Programming—IFC-1010/2020 Programming
81
Table 14: Supervisory/Security Modules
Type ID
Display Label
Type of Device
SACM
ACCESS MONTR
M50xMJ Monitor Module used to monitor a security device. This module is
activated by an open M30xMJ, or XP5-M, or a short condition. Activation of a
module with this Software Type ID will not initiate a security alarm condition:
•
Security Alarm LED will not illuminate.
•
Does not activate trouble status line count on a CRT.
•
No effect on modules programmed as TPND (trouble pending) or GPND
(general event pending).
•
Trouble, clear trouble, or acknowledgements are not reported for this
Type ID.
SARM
AREA MONITOR
M50xMJ Monitor Module, M30xMJ, or XP5-M used to monitor a security
device. This module is activated by either an open or a short condition and
produces a
SECURITY ALARM
message in the display.
SEQM
EQUIP MONTR
M50xMJ Monitor Module, M30xMJ, or XP5-M that functions identically to
Type ID SACM.
SPSU
SPRNKLR MNTR
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit dedicated to a
normally open sprinkler supervisory switch. Activation of a module with
Software Type ID SPSU generates a trouble condition (produces a
SPRNKLR TROUBLE
message) not an alarm. The option of Tracking
(troubles self-restore) is automatically selected for this software type.
SSYM
SYSTEM MONTR
M50xMJ Monitor Module, M30xMJ, or XP5-M used to monitor a security
device. This module is activated by either an open or a short condition and
produces a
SECURITY TAMPER
message in the display.
SUPR
SPRVSRY MNTR
M50xMJ Monitor Module, M30xMJ, XPM-8, or XP5-M circuit dedicated to a
normally open supervisory switch. Activation of a module with Software Type
ID SUPR generates a trouble condition (produces a
SUPRVSRY SIGNAL
message), not an alarm.
Table 15: Evacuation Modules
Type ID
Display Label
Type of Device
EVGA
GN ALARM EVC
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured as a Notification Appliance Circuit, activated on General Alarm, for
NFPA 72 Local Fire Alarm Systems applications.
Note:
This Software Type ID cannot be silenced if a module of Software Type WAT (Water Flow) has been
activated.
Group 6
Group 7