Programming—IFC-1010/2020 Programming
89
Z223
L1M2
M5xCJ
L1M3
(Z223)
DEL(00.00.30(Z223))
Operator:
Equation:
Example:
Z223 has been active for 30 seconds
L1M2 becomes active. L1M2 stays active
for 1 minute and 30 seconds provided that Zone Z223
remains active.
IF
THEN
For delayed operation, the
operator is used.
DEL
L1M3 activates Forward Activating Zone 223 (Z223).
L1M2 CBE is: DEL(00.00.30 00.01.30 (Z223)).
DEL (HH.MM.SS HH.MM.SS (Z1))
Delay
Duration
(optional)
Internal
Equation
0:00
Z223
Inactive
0:30
L1M2
Active
1:00
1:30
2:00
L1M2
Inactive
2:30
delop
Figure 76: DEL Operator
Notes:
•
The entire DEL equation consumes at least 11 bytes (including a
3-byte internal equation) as detailed in the
Size Limitations
section in
this document. The internal equation can be a complex equation many
bytes in size.
•
If a delay of zero is entered (00.00.00), the equation evaluates true as
soon as the internal equation evaluates true and remains that way for
the specified duration, unless the internal equation becomes false.
•
If no duration is specified, then the device is not deactivated until a
reset occurs or the internal equation evaluates false.
DEL