72
Programming—IFC-1010/2020 Programming
????
Level 1 Password
alter66.cdr
^
6
^
6
Figure 66: Key Sequence to Exit Walk Test
This option allows the programmer to exit/abort Walk Test. To exit/abort
Walk Test mode, re-enter Alter Status mode and choose Option 6 from the
Walk Test submenu.
The following example demonstrates exiting/aborting Walk Test:
PRESS 1=SEL,2=UNP,3=UNI,4=TEST,5=UNTST,6=EXIT : 6
Note: Upon exiting/aborting Walk Test, the Walk Test system trouble is
cleared and the IFC-1010/2020 resumes full fire protection.
Activation of smoke detectors during Walk Test for the [Series 500
(x551J)] smoke detectors can be accomplished by placing the optional
Test Magnet (System Sensor
model number M02-24) against the cover
opposite the test module socket, as shown below:
LED
Smkdet1!
Test
Module
So ket
c
Painted
Surface
Painted
Surface
Test
Magnet
Test
Magnet
LED
Figure 67: Placement of Test Magnet for Test (Series 500)
The LEDs should latch within 10 seconds, indicating alarm and
annunciating the panel.
6=EXIT - Exit
Walk Test
Smoke Detector
Activation
During
Walk Test