Programming—IFC-1010/2020 Programming
Programming Software Zones Example
Software Zone 13 programmed as a forward zone to activate two other
software zones (Z15 and Z29), and also mapped to annunciator module
Address 02 Point 05.
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT. INSTALL (BCKSPC TO ABORT) : Z13
ENTER TYPE ID : FZON
ENTER CONTROL-BY-EVENT :(Z15 Z29)
ENTER 20 CHARACTER CUSTOM LABEL : FIRST FLOOR
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR? (Y=YES,N=NO) : Y
ENTER AXXPYY FOR ANNUNCIATOR POINT MAPPING : A2P5
Reverse zones on an IFC-1010/2020 system with the Metasys Fire
Network can be programmed with both CBE and CCBE equations. Below
is an example of Zone 220 programmed as a reverse zone to be activated
by zones on other network nodes.
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT. INSTALL (BCKSPC TO ABORT) : Z220
ENTER TYPE ID : RZON
ENTER CONTROL-BY-EVENT : ( )
* ENTER COOPERATIVE CONTROL-BY-EVENT :
* OR(N8Z1 N8Z2 N8Z3 N8Z4 AND(N9Z1 N9Z2 N9Z3 N9Z4) AND(N10Z1 N10Z2 N10Z3 10Z4))
ENTER 20 CHARACTER CUSTOM LABEL : LIBRARY
DO YOU WANT THIS POINT MAPPED TO AN ANNUNCIATOR? (Y=YES,N=NO) : N
* This item is a Metasys Fire Network specific function and is
programmed only when a SIB-NET is used.