80
Programming—IFC-1010/2020 Programming
Table 13: Output Modules
Type ID
Display Label
Type of Device
CMXC
CMX FORM C
M5x0CJ Control Module configured as a Form-C, M300RJ, XPR-8, or XP5-C
(in Relay mode).
CMXS
CMX CONTROL
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured as a Notification Appliance Circuit.
CON
CONTROL
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode)
configured as a Notification Appliance Circuit.
FORC
FORM C RELAY
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode).
FRCM
FORMC MANUAL
M5x0CJ Control Module configured as a Form-C relay, M300RJ, XPR-8, or
XP5-C (in Relay mode). This device is not deactivated when a system reset
occurs. This module can be used for some fan control applications and can
be mapped only to an AFCM annunciator point.
SPKR
SPEAKER
M5x0CJ Control Module, M300CJ, XPC-8, or XP5-C (in NAC mode) circuit
configured as a speaker circuit.
Note: Each Type ID listed above is prompted for Signal Silence during programming. If the silence option has
been programmed for these devices, they can be turned off using the Control Off function under the Alter
Status menu or by pushing the appropriate annunciator point switch. Of the above types, only CON, FORC,
and SPKR can be silenced by pressing the Signal Silence button, initiating a partial signal silence. The
two tabs on the M5x0CJ must be broken for Form-C relay type devices.
Group 5