3.6
Timer
Due to the timer complexities on the MPRT there are two timer screens. There is a basic timer
control screen and the complex timer control screen. When the user presses the Timer Setup
button anywhere in the TVI the user will be first presented with the basic timer setup screen. This
screen will provide the user with the capability to setup the timer for nearly all relay testing
requirements. If the basic timer setup screen does not provide all the capability required the user
can press the Complex Timer Setup button. This screen will provide the user the capability of
adjusting all the timer input and output setting parameters.
Basic Timer Setup Menu
Figure 26 Basic Timer Setup Menu
Description
Controls
Contact:
The Contact label identifies which input terminal the
associated controls are referring to.
Action
The Action control determines the action of the timer.
The selections are as follows:
Mon(C)
Monitor
Contact
will light the front panel
indicator conditions become true.
Mon(V)
Monitor Voltage will light the front panel
indicator when the conditions become true.
Start
Starts the timer and lights the front
panel indicator when the conditions become true.
Stop
Stops the timer and lights the front panel
indicator when the conditions become true.
CA
Starts the timer when current starts to
be generated.