Figure 82 Timer Input Setup Screen
Pressing the Binary Output Setup button provides a setup screen to modify which output contacts
will simulate the circuit breaker operation.
Figure 83 Binary Output Setup Screen
6.
From the above figure it can be seen that the BINARY OUTPUT Terminals 1 & 2 have
been selected to simulate the circuit breaker 52B and 52A contacts. Pressing the
X
changes the contact to open indicated by the number
0
. Pressing again changes it to be
closed indicated by the number
1
. During the
Fault
simulation
Delay Time
, Binary Output
#1 will be closed, and Binary Output #2 is open. Note that the opposite is true for the
Brk
Trip
simulation. Pressing
Enter
sets the Binary Inputs and Outputs. Pressing
Main Menu
takes you back to the test selection screen.
-